The fouling of cooling tower water was investigated as
a function of heater surface temperature and water quality.
In particular, the effects on fouling of the addition of
calcium in excess of the amounts required for saturation
were examined.
First, the average bulk water temperature was 97 ± 1
degree...
Turbulent mixing across adjacent subchannels in packed rod
bundles was studied using conductivity measurement and sodium
chloride solution as the tracer. Single phase water was the fluid
investigated.
The packed rod bundles were seven stainless steel tubes,
1.905 cm in diameter and 152.4 cm long, arranged in hexagonal close-packed
configuration...
Deposition characteristics of magnesium silicate and calcium carbonate on a heated surface in cooling tower water using city water as make-up was investigated. Flow velocity, bulk temperature and calcium hardness were maintained constant at 5.3 ft/ sec, 95°F and 150 ppm as CaCO₃ respectively whereas surface temperature varied from 105°F...
Scaling characteristics of calcium carbonate on a
heated surface in cooling tower water was investigated.
Bulk temperature was maintained constant at 95°F. Flow
velocities and surface temperatures ranged from 3 ft/sec to
10.3 ft/sec and from 105°F to 170°F respectively. City
water was used as make-up for two different water...
Local and average heat transfer coefficients for heat transfer from internal tubes to a fluidized bed were investigated. A fluidized bed heat exchanger was compared to a baffled and an unbaffled exchanger in terms of power and heat transfer surface area requirements. The fluidized bed heat exchanger consisted of a...
The effects of mass flow rate and subchannel configuration on
the turbulent interchange between adjacent subchannel in simulated
rod bundle were investigated.
The simulated rod bundle was made by arranging seven 1.913 cm
diameter acrylic plastic rods in an equilateral triangular pattern in a
tube 8.89 cm inside diameter.
The...
Various antifoulant treatment programs and the
considerations necessary for the effective use of such
programs were examined.
Two different groups of tests, with and without
iron contamination, have been carried out on the
effectiveness of several of the state-of-the-art
copolymers (PA, HEDP, AA/HPA, AA/MA, SS/MA and AA/SA) in
the inhibition...